Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM05816
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/09/2006 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 11/09/2006 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 11/09/2006 | JWILLIA5 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 11/13/2006 | EGRANT1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 11/13/2006 | EGRANT1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 11/13/2006 | EGRANT1 | WATER | REVIEW | Needs Review | |
| 11/13/2006 | EGRANT1 | FIRE | REVIEW | Needs Review | |
| 11/13/2006 | EGRANT1 | WWM | REVIEW | Needs Review | |
| 11/13/2006 | EGRANT1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 11/13/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |