Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM05814
Parcel: 133350040

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T06CM05814
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Equipment on Equipment 3 is a Microwave on Ckt E-20. Permitted plans call for a description of ""3 UC MICROWAVE" and electrical load of 1.8 KVA. Current revision calls for a description of "3 REC" and an electrical load of 1.0 KVA. Please clarify.
2. Please reinstate Keynote for Equipment 4 on Power Plan, since this is to remain.
3. There appears to be an Equipment Keynote 16 on the Power Plan, which is barely legible due to bubble overwrite. No such equipment on Panel Schedule or Electrical Equipment Feeder Schedule.
4. Provide a circuit for the receptacles on Keynote 11.
5. Please add electrical loads for Ckts E-9, E-11,13, E-15, E-17, E-19, E-21,23,25, E-27,29, E-31,33,55, and E-18, E-20, E-22 E-24 to the panel schedule, and add them to the load calculations on this schedule and on Sheet E0.0. Note that although this will significantly increase connected load, most of this equipment is allowed to be taken at 65% demand per NEC 220.56.
6. Please apply the date to the Revision on the plans. Not only is this required by State law, but it allows us to track which changes were made when.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/09/2008 CPIERCE1 OUT TO CUSTOMER Completed