| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/04/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | T06CM05814 12/4/07 1. Beer Cave East, on E-37,39,41, would draw 38A. The 30A circuit is insufficient. 2. REVIEW INCOMPLETE. CHANGES MADE TO APPROVED PLANS WHICH WERE NOT BUBBLED ON REVISION. THUS THESE PLANS CAN NOT BE REVIEWED OVER THE COUNTER. GIVE OK TO SUBMIOT. |