Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T06CM05814
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/24/2007 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/24/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM05814 1/24/07 1. It appears that load added to this project is 59.5 KVA, not 56.1, and 410a, not 401. Would overload 400A service indicated by load summary. 2. Load Summary indicated 400A service. CT Can on line diagram indicates 600A. Please clarify. |
| 01/24/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 01/24/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Show how the ice x machine is to be drained. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/26/2007 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 01/26/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 01/26/2007 | DELMA ROBEY | REJECT SHELF | Completed |