Permit Number: T06CM05814
Parcel: 133350040

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T06CM05814
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/24/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
01/24/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM05814 1/24/07

1. It appears that load added to this project is 59.5 KVA, not 56.1, and 410a, not 401. Would overload 400A service indicated by load summary.
2. Load Summary indicated 400A service. CT Can on line diagram indicates 600A. Please clarify.
01/24/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
01/24/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Show how the ice x machine is to be drained.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/26/2007 DELMA ROBEY APPROVAL SHELF Completed
01/26/2007 DELMA ROBEY OUT TO CUSTOMER Completed
01/26/2007 DELMA ROBEY REJECT SHELF Completed