Permit Number: T06CM05801
Parcel: 11710041A

Address:
406 N CHURCH AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM05801
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/22/2006 DAVE MANN FIRE REVIEW Approved
11/27/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/27/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
11/28/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
11/30/2006 MARTY DUPONT ADA REVIEW Denied This project has been reviewed by the Office of Equal Opportunity Programs for compliance with the Department of Justice 28 CFR Part 36 ADA Standards for Accessible Design revised July 1, 1994.

1. Alterations to comply with §4.1.6.

2. Provide alarms as required by §4.28 if building is equiped with a central alarm system.

3. Provide location and details of required signage at entrances and restrooms. All signage to comply with §4.30.

4. The existing doors scale 2'-8" and the door schedule is incomplete. A 32" door provides 29" of clear width a minimum of 32" is required. Demonstrate that at each door opening there is 32" of clear width minimum.

5. The top of the existing counter in room 109-Kitchen is not dimensioned. Demonstrate that the rim of the sink is mounted at 34" a.f.f. §4.24. and the faucet controls comply with §4.2 for reach and §4.27 for operation.

6. Details 2 & 3 on sheet A1.2- Change the toilet height dimension to, 17" to 19" TO TOP OF SEAT. §4.16.3, Fig. 29(b)

7. Details 2 & 3 on sheet A1.2- Show a dimension for the height of the toilet paper dispenser. §4.16.6, Fig. 29(b)

8. Detail 6 on sheet A1.2- Identify which side is "Office" & "Lobby". Demonstrate on the Lobby side how the surface protrudes no more than 4" from the face of wall.

9. Provide door hardware information, all hardware to comply with §4.13.9.

10. Door 104.2 is scheduled to be replaced by a 3'-0"x 7'-0" door but scales 2'-6".
11/30/2006 SREEVES1 WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/04/2006 SUE REEVES OUT TO CUSTOMER Completed
12/04/2006 SUE REEVES REJECT SHELF Completed