Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T06CM05801
Parcel: 11710041A

Address:
406 N CHURCH AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM05801
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 5/19/06
ACTIVITY NUMBER: T06CM02118
PROJECT NAME: T.I. Inspectors office space Development Services
PROJECT ADDRESS: 406 N. Church
ARCHITECT / ENGINEER: Lizard Rock Designs
PROJECT REVIEWER: Christy Foreman

1) PROVIDE CLEAR TURNING RADIUS AT BACK DOOR PER ANSI A117.1 2003 SECTION 405.7.5.
2) PROVIDE CLARIFICATION THAT THE BREAKROOM COUNTER IS PER ANSI A117.1 2003 PER SECTION 1003.12.4.2
3) CLARIFY DEPTH OF FOOTING BELOW GRADE FOR NE COLUMNS.
4) CLARIFY ON DETAIL 2/S1.0 LOCATION OF BASE OF WALL REINFORCEMENT PER STRUCTURAL CALCULATIONS. sPACING 16" O.C.
5) CLARIFY ON DRAWINGS DIMENSIONS BETWEEN COLUMNS / BEAM SPAN TO JUSTIFY STRUCTURAL CALCULATIONS. SHT. A1.0 DOES NOT SHOW INFORMATION AND SHT. S2.0 DOES NOT SPECIFY. NEED TO CLARIFY SPAN AND OVERHANG PER STRUCTURAL CALCULATIONS.
6) CLARIFY IF THERE IS A CONNECTION FOR OVERHANG OF NEW STEEEL BEAM TO EXISTING STEEL BEAM.
11/14/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/14/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Provide a disconnecting means for the Power Door Opener.
2. Allowed lumens according to the Tucson Lighting Code appears to be 57,000, not 5,700.
11/14/2006 ROBERT SHERRY WATER REVIEW Approved
11/14/2006 HEATHER THRALL ZONING REVIEW Approved
11/14/2006 DAVE MANN FIRE REVIEW Denied Provide documentation that doors are 1-hour rated (with closers) to comply with the exceptions to travel distances according to IBC 2003, Section 1014.2.1. Otherwise, building must be sprinklered.
11/14/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1.Provide an accessible drinking fountain. Reference Chapter 2900, IBC 2003.
2. Water heaters without integral heat traps shall have the first 8' of piping insulated per Section 804.5, IECC 2003. Clarify if the pipe insulation specification on sheet MP1 applies to this activity.
11/17/2006 SREEVES1 WWM REVIEW Needs Review
11/17/2006 SREEVES1 ADA REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/17/2006 SUE REEVES OUT TO CUSTOMER Completed