Permit Number: T06CM05775
Parcel: 113043310

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM05775
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/21/2006 BETSY COTTLE COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/24/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
11/24/2006 ROBERT SHERRY WATER REVIEW Passed
11/24/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations demonstrating adequate ventilation for the new use. Reference Section 401.2, IMC 2003.
2. Provide sealed drawings.
12/04/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied Provide copy of approved plans for current electrical installation. Reference drawing feeder load calculation total appears to exceed the capacity of the service.
12/07/2006 GERRY KOZIOL WWM REVIEW Passed
12/11/2006 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) TABLE 2902.1 OF THE 2003 IBC REQUIRES ONE WATER CLOSET PER 15 PEOPLE, ONE LAVATORY PER 15 PEOPLE AND SEPERATE TOILET FACILITIES FOR STAFF.

2) PROVIDE A WATER FOUNTAIN PER TABLE 2902.1 OF IBC.

3) VAN ACCESSIBLE H.C. PARKING SPACE TO BE 132" WIDE WITH 60" ACCESS AISLE OR 96" WIDE WITH 96' ACCESS AISLE PER ANSI A117.1 SECTION 502.2.

4) AS INTERIOR FRAMING WAS PREVIOUSLY DONE WITHOUT PERMITS WE NEED TO LOOK AT IT AS NEW WORK. PLEASE DELETE "EXISTING" REFERENCE IN YOUR WALL SCHEDULE.