| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/21/2006 | BETSY COTTLE | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/24/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 11/24/2006 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 11/24/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations demonstrating adequate ventilation for the new use. Reference Section 401.2, IMC 2003. 2. Provide sealed drawings. |
| 12/04/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Provide copy of approved plans for current electrical installation. Reference drawing feeder load calculation total appears to exceed the capacity of the service. |
| 12/07/2006 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 12/11/2006 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1) TABLE 2902.1 OF THE 2003 IBC REQUIRES ONE WATER CLOSET PER 15 PEOPLE, ONE LAVATORY PER 15 PEOPLE AND SEPERATE TOILET FACILITIES FOR STAFF. 2) PROVIDE A WATER FOUNTAIN PER TABLE 2902.1 OF IBC. 3) VAN ACCESSIBLE H.C. PARKING SPACE TO BE 132" WIDE WITH 60" ACCESS AISLE OR 96" WIDE WITH 96' ACCESS AISLE PER ANSI A117.1 SECTION 502.2. 4) AS INTERIOR FRAMING WAS PREVIOUSLY DONE WITHOUT PERMITS WE NEED TO LOOK AT IT AS NEW WORK. PLEASE DELETE "EXISTING" REFERENCE IN YOUR WALL SCHEDULE. |