Permit Number: T06CM05751
Parcel: 111070070

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T06CM05751
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2007 PETER MCLAUGHLIN ZONING-CITY HALL REVIEW Denied Revise plans to demonstrate compliance with special exception conditions a. through e. for special exception case SE-06-34.

1) Condition a. requires that the face of each array shall be no greater than 8 feet in length. The plans indicate the dimension of the arrays to be 12 feet. Revise plan drawings
and details.

2) Condition b. requires wire ports to be no higher or lower than antenna panels and that cables be routed through the interior of the pole and not be visible. Add a note to the plan or additional details demonstrating compliance.

3. Provide a copy of approved site plan for existing monopole and related equipment to demonstrate compliance with special exception condition c.

4. Dimension pole at base, top and point of attachment per conditon d.

5. Add a note to the elevation drawings stating that all new equipment shall be painted to match the existing pole per condition e.
01/09/2007 JAY HOGAN OPERATIONS REVIEW Approved
12/12/2006 DAVE MANN FIRE REVIEW Approved
12/14/2006 BETSY COTTLE COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
01/24/2007 FSANCHE1 OUT TO CUSTOMER Completed