Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM05704
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/02/2006 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
11/02/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide a smoke detector for the west rooftop unit (>2000 CFM) |
11/02/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM05704 11/2/06 1. Coordinate Water Heater requirements with Mechanical. Sheet P-1 WH-2 is 230/1/60, 3600W. Electrical calls for 3-120/1/60 3000W InstaHots. 2. Fill in load information on panel schedule for Ckt B-36. Is InstaHot on Power Plan. 3. Service load is 348A at 0.85 pf, not 296A. |
11/02/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/02/2006 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/02/2006 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
11/02/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
11/02/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
11/07/2006 | DROBEY1 | WWM | REVIEW | Needs Review | |
11/07/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |