Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM05704
Parcel: 11301146Z

Address:
1773 E PRINCE RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM05704
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/02/2006 MICHAEL ST. PAUL ZONING REVIEW Approved
11/02/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide a smoke detector for the west rooftop unit (>2000 CFM)
11/02/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM05704 11/2/06

1. Coordinate Water Heater requirements with Mechanical. Sheet P-1 WH-2 is 230/1/60, 3600W. Electrical calls for 3-120/1/60 3000W InstaHots.
2. Fill in load information on panel schedule for Ckt B-36. Is InstaHot on Power Plan.
3. Service load is 348A at 0.85 pf, not 296A.
11/02/2006 ROBERT SHERRY WATER REVIEW Approved
11/02/2006 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
11/02/2006 PAUL MACHADO ENGINEERING REVIEW Approved
11/02/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/02/2006 DAVE MANN FIRE REVIEW Approved
11/07/2006 DROBEY1 WWM REVIEW Needs Review
11/07/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/07/2006 DELMA ROBEY OUT TO CUSTOMER Completed