Permit Number: T06CM05685
Parcel: 12513020C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM05685
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/01/2006 MARTIN BROWN FIRE REVIEW Approved
11/01/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Confirm that the gas train for the generator set meets the requirements of NFPA 37.
11/01/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
11/01/2006 ROBERT SHERRY WATER REVIEW Approved
11/01/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the energy value of the natural gas; Southwest gas does not provide gas with 1100 BTU/CF.
2. Provide a riser diagram for the gas piping to clarify the actual developed pipe lengths used in the calculations.
3. Provide information to show that the existing roof-top units can use an input pressure of 11-14"WG or provide secondary regulation of the gas pressure.
11/01/2006 RSHERRY1 WWM REVIEW Passed
11/01/2006 PATRICIA GILBERT ENGINEERING REVIEW Approved
11/03/2006 EGRANT1 BUILDING-COMMERCIAL REVIEW Needs Review
11/03/2006 EGRANT1 ZONING REVIEW Needs Review
11/03/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review