| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/01/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/01/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Confirm that the gas train for the generator set meets the requirements of NFPA 37. |
| 11/01/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 11/01/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/01/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the energy value of the natural gas; Southwest gas does not provide gas with 1100 BTU/CF. 2. Provide a riser diagram for the gas piping to clarify the actual developed pipe lengths used in the calculations. 3. Provide information to show that the existing roof-top units can use an input pressure of 11-14"WG or provide secondary regulation of the gas pressure. |
| 11/01/2006 | RSHERRY1 | WWM | REVIEW | Passed | |
| 11/01/2006 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 11/03/2006 | EGRANT1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 11/03/2006 | EGRANT1 | ZONING | REVIEW | Needs Review | |
| 11/03/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |