Review Date Reviewer's Name Type of Review Description Status Comments
07/02/2007 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Tucson Dodge
T06CM05677
Site Plan (3rd Review)

TRANSMITTAL DATE: July 2, 2007

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for full code compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC).

2. Zoning acknowledges the receipt of the approved Combo Request and the completed Covenant Regarding Development and Use of Real Property. Zoning could not locate the recordation information, docket and page, for the Covenant Regarding Development and Use of Real Property. Please provide.

3. This comment was not addressed. Per Development Standard D.S. 2-02.2.1.A.25 provide existing and proposed freestanding lighting layout and type on the site plan. Provide a detail; list the height of pole and type of lighting.

4. Ensure that all changes to the site plan are reflected on the landscape & grading plan.

5. Zoning agrees to provide an over the counter review once the above comments have been addressed. Please call or email to set an appointment for this review.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\site\t06cm05677-3rd.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
07/02/2007 STEVE SHIELDS ZONING HC SITE REVIEW Approved
07/08/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: July 9, 2007
ACTIVITY NUMBER: T06CM05677
PROJECT NAME: Tucson Dogde
PROJECT ADDRESS: 4220 East 22nd Street
PROJECT REVIEWER: Patricia Gilbert, Engineering Associate

The following items must be revised or added to the site plan. Please include a response letter with the next submittal that states how all comments have been addressed.


RESUBMITTAL REQUIRED: SITE PLAN

1. 6' wide sidewalk is required within the ROW along an arterial road per the Major Street & Route Plan. It is acknowledged the existing sidewalk along 22nd Street is 5'. The project is a full code compliance review, that said 6' sidewalk is required along the entire length of 22nd Street. Revise the site plan to show new 6' sidewalk along the entire length of 22nd Street. DS 2-02.2.1.A.8., DS 3-01
07/12/2007 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. Vegetation or structures higher than thirty (30) inches must be located outside of the sight visibility triangle. Plant materials located within sight visibility triangles should consist of ground cover or low growing vegetation. Caesalpinia mexicana (10'-15' height and spread) and Cassia nemophila (4'-6' height and spread) will typically grow in excess of 30". Revise location of plant materials as necessary

2. Include inside dimensions of diamond planter within customer parking on the landscape, site and grading plans. An unpaved planting area, which is a minimum of thirty-four (34) square feet in area and four (4) feet in width, must be provided for each canopy tree per DS 2-06.3.3.C.

3. Landscape plan shall include irrigation specification design and layout per DS 2-07.5.4.A & DS 2-07.5.4.B including source of irrigation, sleeves for driveways and sidewalks, locations of valves, low-flow bubblers or drip irrigation. Provide irrigation layout on landscape plan or separate sheet.

4. All landscape areas will be depressed to accept water flow from roofs, PAAL, and parking areas. Show by detail or spot elevations how landscape areas will accommodate water harvesting.
07/13/2007 ANDREW CONNOR NPPO REVIEW Approved
07/24/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the site drawing to include the following information:
a. the location and size of the water meter
b. the location of the main water lines and fire hydrants
c. The location of any gas meters
d. the location and size of the public sanitary sewer and
e. the location, invert, and rim elevation of all manholes and cleanouts
Reference City of Tucson Development Standard No. 2-05.0 2.3 and Section 103.2.3, UPC 2003.
2. Show the location of the proposed point of connection for the building sewer to the public sewer. Reference Section 103.2.3, UPC 2003.