Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/07/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM05655 12/7/06

1. Show electrical loads for new receptacles.
2. Provide Panel Schedule and feeder load calculations.
12/07/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
12/29/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1. Identify different tenants and start permit for suite 105.
2. Provide code data ie occupancies, building type, allowable area, occupant load, 20% accessiblity etc., see code analysis sht. provided to client.
3. Provide details for ramp, signs, and striping for accessibility.
4) Clarify location of new hardware to justify $1659.00. Hardware only counts for accessibility if it is on the accessible route. See chapter 11 of 2003 IBC.
5) Clarify/ justify corridor to beauty salon and alteration complies with ANSI 2003 A117.1 for the accessible route to these tenants.