| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/12/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/07/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM05655 12/7/06 1. Show electrical loads for new receptacles. 2. Provide Panel Schedule and feeder load calculations. |
| 12/07/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 12/29/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Identify different tenants and start permit for suite 105. 2. Provide code data ie occupancies, building type, allowable area, occupant load, 20% accessiblity etc., see code analysis sht. provided to client. 3. Provide details for ramp, signs, and striping for accessibility. 4) Clarify location of new hardware to justify $1659.00. Hardware only counts for accessibility if it is on the accessible route. See chapter 11 of 2003 IBC. 5) Clarify/ justify corridor to beauty salon and alteration complies with ANSI 2003 A117.1 for the accessible route to these tenants. |