Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM05655
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/30/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
10/30/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Calculate the required amount of outside air for each occupancy per Section 403.3, IMC 2003. Use Section 403.3.2, IMC 2003 to adjust the required amount of outside air needed for common supply to different occupancies. |
10/30/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
10/30/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/30/2006 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | See permit 5654 |
10/30/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
12/01/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
12/07/2006 | GERRY KOZIOL | WWM | REVIEW | Passed | |
12/07/2006 | CAGUILA1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
12/07/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |