Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/12/2007 | FSANCHE1 | WWM | REVIEW | Needs Review | |
01/12/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
12/07/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
12/07/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM05654 12/7/06 1. Show electrical loads for all branch circuits. 2. Provide Panel Schedule and feeder load calculations. 3. Provide Electrical Line Diagram of electrical service and distribution. 4. Provide service load calculations. 5. Provide an electrical circuit for the new Heat Pump maintenance receptacle. 6. It appears that the Ground Fault and Short Circuit Protection for the New Heat Pump is oversized. Please provide manufacturer cut sheets. |
12/29/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Identify different tenants and start permit for suite 105. 2. Provide code data ie occupancies, building type, allowable area, occupant load, 20% accessiblity etc., see code analysis sht. provided to client. 3. Provide details for ramp, signs, and striping for accessibility. 4) Clarify location of new hardware to justify $1659.00. Hardware only counts for accessibility if it is on the accessible route. See chapter 11 of 2003 IBC. 5) Clarify/ justify corridor to beauty salon and alteration complies with ANSI 2003 A117.1 for the accessible route to these tenants. |