Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM05654
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/30/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
10/30/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Calculate the required amount of outside air for each occupancy per Section 403.3, IMC 2003. Use Section 403.3.2, IMC 2003 to adjust the required amount of outside air needed for common supply to different occupancies. |
10/30/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
10/30/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/30/2006 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Identify different tenants 2. Provide code data ie occupancies, building type, allowable area, occupant load, 20% accessiblity etc.. 3. Detail interior walls including bracing |
10/30/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
12/01/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
12/07/2006 | CAGUILA1 | WWM | REVIEW | Needs Review | |
12/07/2006 | CAGUILA1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
12/07/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |