Permit Number: T06CM05598
Parcel: 11309224A

Address:
865 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM05598
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/15/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Demonstrate that NEC 240.21 (C) is not violated. THIS COMMENT WAS MADE ON THE FIRST SUBMITTAL. Compliance is not possible to determine without solid knowledge of conductor sizing of the transformer secondary. Keynote 6 on Sheet E-4.0 calls out 4 sets of 3/0. The fault calculations on the same sheet call out for one set of 4/0. On Sheet E-1.0, the Elevation calls out 2 sets of 600 kcmil.
2. Load Calculations reference both APS and TEP as sources for demand information. Please check your references, and double check the information itself.
3. Fault calculations call out 4/0 for the Panel PE feeder. Keynote 5 calls out #1. Please clarify.
4. Fault calculations resultant is greater than 10,000A for Panel PE. This Panel is only rated for 10,000A. Please correct.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/19/2006 DELMA ROBEY OUT TO CUSTOMER Completed
12/19/2006 SUE REEVES REJECT SHELF Completed