Permit Number: T06CM05598
Parcel: 11309224A

Address:
865 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM05598
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2006 DAVE MANN FIRE REVIEW Approved
10/27/2006 BETSY COTTLE COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/31/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/31/2006 RSHERRY1 WWM REVIEW Passed
10/31/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/31/2006 ROBERT SHERRY WATER REVIEW Approved
11/20/2006 LINHART PETERSEN POERS ASSOC. BUILDING-COMMERCIAL REVIEW Approved
11/22/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Indicate the location of New Panel PE.
2. Indicate the location of the gutter between the 225 KVA X'FMR and the panels.
3. Provide the conductor size in the run between the 225 KVA X'FMR and the gutter.
4. Demonstrate that NEC 240.21 (C) is not violated.
5. Provide the values of the overcurrent protective devices in the mains of Panels PA and PB.
6. Demonstrate compliance with NEC Table 450.3 (B) Note 2.
7. Load Calculation Information Note B refers to calculations on Sheet E-4.0. There are no such calculations on that sheet.
8. PE-21 powers the Copy Machine according to the Power Plan. This circuit is a spare on the panel schedule.
9. It appears that the load on Ckt 5 is 360VA, not 180.
10. Schedule for New Panel PE calls this MLO. Single Line Diagram indicates a MCB. Please clarify.
11. On Sheet E-4.0, the #8 GR on Keynote 5 should be a #6. Reference NEC Table 250.66.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/04/2006 CINDY AGUILAR OUT TO CUSTOMER Completed
12/04/2006 SUE REEVES REJECT SHELF Completed