Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM05594
Parcel: 10610005A

Address:
2020 W PRINCE RD

Review Status: Active

Review Details: POST 3RD PARTY REVIEW

Permit Number - T06CM05594
Review Name: POST 3RD PARTY REVIEW
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2008 ROBERT SHERRY WATER REVIEW Approved
05/06/2008 DAVE MANN FIRE REVIEW Approved
05/09/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
05/12/2008 GERRY KOZIOL WWM REVIEW Approved
05/13/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: American Home Furnishings - Warehouse Expansion
T06CM05594
Building Plan (1st Review)

TRANSMITTAL DATE: May 13, 2008

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t06cm05594.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
05/13/2008 LOREN MAKUS ENGINEERING REVIEW Denied Site plan must be approved before building plan is approved.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/14/2008 SHANAE POWELL REJECT SHELF RECEIVED