Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM05556
Parcel: 14042075B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM05556
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/16/2006 STEVE SHIELDS ZONING REVIEW Approved
11/16/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how the air supplied to the restroom is prevented from being recirculated. Reference Section 403.2, IMC 2003.
2. Show that adequate outside air is being supplied to the space. Reference Section 403.3, IMC 2003.
11/16/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
11/16/2006 ROBERT SHERRY WATER REVIEW Approved
11/16/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved 1)CLARIFY SEPARATED USE ON BUILDING PLAN AND SPECIFY FIRE RATING.
11/16/2006 RSHERRY1 WWM REVIEW Passed
11/16/2006 DAVE MANN FIRE REVIEW Approved
11/20/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Passed T06CM05556 11/16/06

1. Electrical load calculations, using the 40% factor, are valid for dwelling units. This is not a dwelling unit. Reference NEC 220.30.
2. Add receptacle outlets ot load calculations. Reference NEC 220.3 (9).
3. Add track lighting to feeder calculations. Fererence NEC 220.12 (B).
4. Demonstrate that no phase of panel is being overloaded.
5. Denote voltage, phase, and fault current rating of new panel.
6. Provide electrical line diagram.
7. Demonstrate that service is not overloaded.
8. Provide available fault current and fault calculations.
11/28/2006 DROBEY1 ENGINEERING REVIEW Needs Review
11/28/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/28/2006 DELMA ROBEY APPROVAL SHELF Completed
11/28/2006 DELMA ROBEY OUT TO CUSTOMER Completed
11/28/2006 DELMA ROBEY REJECT SHELF Completed