Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM05547
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/20/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 10/20/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
| 10/20/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | 1) JUSTIFY WITH STRUCTURAL CALCUALTIONS FOR NEW HVAC ON ROOF. |
| 10/20/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
| 10/25/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show how the ductwork has been sized. 2 The minimum font size is 1/8", all upper case. |
| 10/25/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T06CM05547 10/20/06 Please change all references to the IRC to NEC. |
| 10/25/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/25/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the natural gas piping to support the new load. Show the route of the existing piping and meter location. 2. The minimum font size is 1/8", all caps |
| 10/25/2006 | RSHERRY1 | WWM | REVIEW | Passed | |
| 11/16/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/16/2006 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 11/16/2006 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 11/16/2006 | DELMA ROBEY | REJECT SHELF | Completed |