Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T06CM05547
Parcel: 121063160

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM05547
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/20/2006 HEATHER THRALL ZONING REVIEW Approved
10/20/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
10/20/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved 1) JUSTIFY WITH STRUCTURAL CALCUALTIONS FOR NEW HVAC ON ROOF.
10/20/2006 DAVE MANN FIRE REVIEW Approved
10/25/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how the ductwork has been sized.
2 The minimum font size is 1/8", all upper case.
10/25/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T06CM05547 10/20/06

Please change all references to the IRC to NEC.
10/25/2006 ROBERT SHERRY WATER REVIEW Approved
10/25/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the natural gas piping to support the new load. Show the route of the existing piping and meter location.
2. The minimum font size is 1/8", all caps
10/25/2006 RSHERRY1 WWM REVIEW Passed
11/16/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/16/2006 DELMA ROBEY APPROVAL SHELF Completed
11/16/2006 DELMA ROBEY OUT TO CUSTOMER Completed
11/16/2006 DELMA ROBEY REJECT SHELF Completed