Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM05479
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/17/2006 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
10/17/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/17/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM05479 10/17/06 1. Please show the location of Panel A on the plans. 2. Please note that according to TEP SR-510, the available fault current for a 1200A 120/208V service is typically 75,100A, not 55,600. 3. Please provide IECC Lighting Power Budget calculations for this occupancy. |
10/17/2006 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
10/17/2006 | JWILLIA5 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
10/24/2006 | DROBEY1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
10/24/2006 | DROBEY1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
10/24/2006 | DROBEY1 | WWM | REVIEW | Needs Review | |
10/24/2006 | DROBEY1 | FIRE | REVIEW | Needs Review | |
10/24/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/24/2006 | DELMA ROBEY | OUT TO CUSTOMER | Completed |