Permit Number: T06CM05479
Parcel: 10511040D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM05479
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/17/2006 STEVE SHIELDS ZONING REVIEW Approved
10/17/2006 ROBERT SHERRY WATER REVIEW Approved
10/17/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM05479 10/17/06

1. Please show the location of Panel A on the plans.
2. Please note that according to TEP SR-510, the available fault current for a 1200A 120/208V service is typically 75,100A, not 55,600.
3. Please provide IECC Lighting Power Budget calculations for this occupancy.
10/17/2006 PATRICIA GILBERT ENGINEERING REVIEW Approved
10/17/2006 JWILLIA5 BUILDING-COMMERCIAL REVIEW Needs Review
10/24/2006 DROBEY1 MECHANICAL-COMMERCIAL REVIEW Needs Review
10/24/2006 DROBEY1 PLUMBING-COMMERCIAL REVIEW Needs Review
10/24/2006 DROBEY1 WWM REVIEW Needs Review
10/24/2006 DROBEY1 FIRE REVIEW Needs Review
10/24/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/24/2006 DELMA ROBEY OUT TO CUSTOMER Completed