Permit Number: T06CM05475
Parcel: 11306045A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM05475
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/17/2006 HEATHER THRALL ZONING REVIEW Approved
10/17/2006 ANY ENGINEERING REVIEW Approved
10/18/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE CODE ANALYSIS CLARIFYING SEPARATED / NON-SEPARATED USE AND MOST RESTRICTIVE USE. ACTUAL SQ. FOOTAGE OF BUILDING.
2) PROVIDE ACCESSIBILTY TO SINK PER ANSI A117.1 2003 TOP OF COUNTER SHALL 34"
3) CLARIFY ACCESSIBLE ROUT FROM PARKING INTO BUILDING.
10/18/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify which heat pump serves which area in the building.
2. Clarify the ventilation calculations with respect to the individual units.
3. What is the weight of the old RTU units as compared to the new units?
4. Provide an electrical design.
10/18/2006 MARTIN BROWN FIRE REVIEW Approved
10/18/2006 ROBERT SHERRY WATER REVIEW Approved
11/03/2006 GBONILL1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
11/03/2006 GBONILL1 WWM REVIEW Needs Review
11/03/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
11/03/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved