Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM05475
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/17/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 10/17/2006 | ANY | ENGINEERING | REVIEW | Approved | |
| 10/18/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE CODE ANALYSIS CLARIFYING SEPARATED / NON-SEPARATED USE AND MOST RESTRICTIVE USE. ACTUAL SQ. FOOTAGE OF BUILDING. 2) PROVIDE ACCESSIBILTY TO SINK PER ANSI A117.1 2003 TOP OF COUNTER SHALL 34" 3) CLARIFY ACCESSIBLE ROUT FROM PARKING INTO BUILDING. |
| 10/18/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify which heat pump serves which area in the building. 2. Clarify the ventilation calculations with respect to the individual units. 3. What is the weight of the old RTU units as compared to the new units? 4. Provide an electrical design. |
| 10/18/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/18/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/03/2006 | GBONILL1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 11/03/2006 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 11/03/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 11/03/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |