Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM05445
Parcel: 128041190

Review Status: Completed

Review Details: RESIDENTIAL BLDG-MODEL PLAN/ENGINE/WALK THRU

Permit Number - T06CM05445
Review Name: RESIDENTIAL BLDG-MODEL PLAN/ENGINE/WALK THRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/13/2006 HEATHER THRALL ZONING REVIEW Approved
10/13/2006 PATRICIA GILBERT ENGINEERING REVIEW Approved
10/13/2006 HEATHER THRALL NPPO REVIEW Passed
10/20/2006 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Approved
10/31/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T06CM05445 10/24/06

1. Show location of all equipment on scaled drawing.
2. Provide rating of Main Circuit Breaker to new All-In-One.
3. Show existing equipment and where the new intercepts the existing.
4. Show the interconnection of the photovoltaic system on the line diagram.
5. Provide overcurrent protection for the circuits on the line diagram.
6. Define the rectangular boxes shown on the line diagram.
7. Provide TEP available fault current at the upgraded electrical service.
8. Provide fault current rating of new and existing equipment.

THIS IS AN INCOMPLETE REVIEW. SEE THE ATTACHED ELECTRICAL PERMITTING REQUIREMENTS.