Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG-MODEL PLAN/ENGINE/WALK THRU
Permit Number - T06CM05445
Review Name: RESIDENTIAL BLDG-MODEL PLAN/ENGINE/WALK THRU
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/13/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 10/13/2006 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 10/13/2006 | HEATHER THRALL | NPPO | REVIEW | Passed | |
| 10/20/2006 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Approved | |
| 10/31/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T06CM05445 10/24/06 1. Show location of all equipment on scaled drawing. 2. Provide rating of Main Circuit Breaker to new All-In-One. 3. Show existing equipment and where the new intercepts the existing. 4. Show the interconnection of the photovoltaic system on the line diagram. 5. Provide overcurrent protection for the circuits on the line diagram. 6. Define the rectangular boxes shown on the line diagram. 7. Provide TEP available fault current at the upgraded electrical service. 8. Provide fault current rating of new and existing equipment. THIS IS AN INCOMPLETE REVIEW. SEE THE ATTACHED ELECTRICAL PERMITTING REQUIREMENTS. |