Permit Number: T06CM05435
Parcel: 130100790

Address:
3265 E 24TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM05435
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/09/2007 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Activity # T06CM05435
Date: 3/9/07

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

STRUCTURAL PLANS:
1. Show masonry wall lateral support (horizontal and vertical R606.8.1, R606.8.2).
2. Show bond beam, 2 #4 rebar continuous (R606.10).
3. Submit truss calculations, signed, dated and wet-sealed by an Arizona registered engineer. Truss calculations shall be cross-referenced to the floor plans.
4. Specify the outrigger & gable end bracing and connections to the structure.
5. Specify and detail all over-framing connections for intersecting pitched roof assemblies. Provide a minimum opening of 22" by 30" for access and ventilation between over-framed assemblies (>30 S.F.), R807.

SECTIONS - DETAILS - MISC. NOTES:
1. On standard detail sheets, cross out all details that do not apply or are not being used.
2. Additional details for the porch are required:
· Beam to beam connection at SE corner of porch
· Post or beam pocket at NE corner of porch
· Continuous load path for shear transfer (Roof diaphragm to wall)

OUTDOOR LIGHTING CODE:
1. Show compliance with City of Tucson Outdoor Lighting Code;
Total property lighting limit for area E3 is 55,000 lumens per acre and the unshielded limit for area E3 is 12,000 lumens per acre. Include all exterior fixtures on the property in the calculations.
Review guidance: www.ci.tucson.az.us/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf
(12,000 unshielded lumens per acre x 0.16 acre = 1920 lumens)

If you have any questions, please contact:
Clayton Trevillyan
791-5550 ext. 1113

Final Status

Task End Date Reviewer's Name Type of Review Description
03/16/2007 FSANCHE1 OUT TO CUSTOMER Completed
03/16/2007 SUE REEVES REJECT SHELF Completed