Review Status: Completed

Review Details: OTHER

Permit Number - T06CM05412
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/29/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied Provide overcurrent protection for the Photovoltaic Source Circuits. Reference NEC 698.9 (A). The discussion in your response is very thorough and accurate. However, I still need to see the manufacturer certification of zero feedback from the inverter. I looked and did not find such documentation in the cut sheet information I was able to download on first review.

Would like to see manufacturer information such that (+) ground is verifiable. This was not real clear form the block diagram that was submitted, but I'm willing to discuss.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/09/2007 SUE REEVES OUT TO CUSTOMER Completed
02/09/2007 SUE REEVES REJECT SHELF Completed