Permit Number: T06CM05405
Parcel: 133243690

Address:
100 N PANTANO RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM05405
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
01/25/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Provide specifications and cut sheets for the electrical load referred to as "NEON." Second Request.
2. Provide cut sheets for Fixtures A and B. The AF fixtures I was able to find on the Lithonia site is a Heavy Duty Industrial fixture. Not listed for damp location. Not recessed mounting.
3. Reference Outdoor Lighting Calculations. There is no Note 401.5. Please clarify.
4. It is doubtful that the fixtures accounted for in the Outdoor Lighting Calculations entail an entire site inventory. This would imply that there is no parking lot lighting, pedestrian bollards, or other building lighting.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/30/2007 DELMA ROBEY APPROVAL SHELF Completed
01/30/2007 DELMA ROBEY OUT TO CUSTOMER Completed
01/30/2007 GERARDO BONILLA REJECT SHELF Completed