Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T06CM05405
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/11/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/25/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Provide specifications and cut sheets for the electrical load referred to as "NEON." Second Request. 2. Provide cut sheets for Fixtures A and B. The AF fixtures I was able to find on the Lithonia site is a Heavy Duty Industrial fixture. Not listed for damp location. Not recessed mounting. 3. Reference Outdoor Lighting Calculations. There is no Note 401.5. Please clarify. 4. It is doubtful that the fixtures accounted for in the Outdoor Lighting Calculations entail an entire site inventory. This would imply that there is no parking lot lighting, pedestrian bollards, or other building lighting. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/30/2007 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 01/30/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 01/30/2007 | GERARDO BONILLA | REJECT SHELF | Completed |