Permit Number: T06CM05402
Parcel: 107040130

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM05402
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2006 DAVE MANN FIRE REVIEW Approved
10/11/2006 PATRICIA GILBERT ENGINEERING REVIEW Approved per JG
10/12/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
10/20/2006 HEATHER THRALL ZONING REVIEW Approved
10/23/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM05402 10/23/06

1. MOCP on HP2 and HP3 are 60A and 70A respectively, but their breakers are 70A and 80A respectively.
2. Load calculations for Panel L1 appear to apply demand factors to receptacle loads computed at greater than 180VA. Reference NEC 220.13.
3. If L2 is powered via L1 with feed-through lugs, please indicate such on the plans.
10/25/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/25/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/25/2006 ROBERT SHERRY WATER REVIEW Approved
10/25/2006 RSHERRY1 WWM REVIEW Passed
11/01/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review