Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM05402
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/11/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
| 10/11/2006 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | per JG |
| 10/12/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/20/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 10/23/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM05402 10/23/06 1. MOCP on HP2 and HP3 are 60A and 70A respectively, but their breakers are 70A and 80A respectively. 2. Load calculations for Panel L1 appear to apply demand factors to receptacle loads computed at greater than 180VA. Reference NEC 220.13. 3. If L2 is powered via L1 with feed-through lugs, please indicate such on the plans. |
| 10/25/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/25/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 10/25/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/25/2006 | RSHERRY1 | WWM | REVIEW | Passed | |
| 11/01/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |