Permit Number: T06CM05400
Parcel: 113060380

Address:
2107 E LIND RD

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T06CM05400
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/15/2006 STANTEC 2ND PARTY REVIEW REVIEW Denied December 13, 2006


To: Steve Long, Acting Building Official
City of Tucson Development Services Department
201 N. Stone Avenue, First Floor
Tucson, Arizona 85701

Re: Phillips Residence - Addition
City of Tucson No. T06CM05400
Stantec Project No. 816-30015-01 (089)




Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back-check time, we request that you please provide revised plans and calculations, clouding any changes, along with a written response to each of the noted items indicating the action taken.

SCOPE OF REVIEW:

The scope of this review covers Architectural, Structural, Plumbing, Mechanical, Model Energy and Electrical codes. All code references are to the 2003 International Residential Code (IRC) except for plumbing, which is to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

Note: Be aware that the City of Tucson intends to adopt the 2006 International Residential Code sometime around January 2007 (with the exception of the plumbing portion of the IRC which will likely be substituted with the 2006 Uniform Plumbing Code).

GENERAL:

Please provide a “cleaner” copy of Sheet 2 of 8. The text on the copy we received is very “grainy” and very difficult to read.

ARCHITECTURAL:

Indicate the location of sewer and electrical on the property.

Provide access to each separate attic and crawlspace that exceeds 30 square feet. Designate locations on the drawings. Openings shall not be less than 22” by 30”. The attic access shall provide a minimum of 30” of headroom, and shall be located in a hallway or readily accessible space [2003 IRC Sec. R807].

Note doors between the house and the garage shall be minimum 1-3/8” thick solid core ands shall have a closer [2003 IRC Sec. 309.1].

Ceilings with a truss or joist spacing over 16" o.c. need to be provided with a minimum of either 5/8" gypsum board or 1/2" sag-resistant gypsum board [2003 IRC Sec. Table R702.3.5, Footnote d].

Note and size all roof drains or scuppers on flat-roofed areas [2003 IRC Sec. R903.4 and 2003 IPC Sec. 1106].

Show calculation of attic or rafter ventilation area required and note the location of all vents needed to comply [2003 IRC Sec. R806.2].

Provide detail and specify anchoring method, backing, vapor barrier and support for the brick veneer [2003 IRC Sec. R301.2.2.3].

STRUCTURAL:

In Section B-B shown on Sheet 7 of 8, what is the sheathing that covers the stud framed pony wall placed on top of the existing brick wall? Also how is the pony wall attached to the top plate?

The beam spanning 16’-0” over the garage door opening is slightly undersized as a 4 x 12 DF #2

What are the existing lintels at the existing window openings adjacent to the new porch, and are they capable of taking the additional porch load?

The girder trusses at the garage are spaced 10’-0” o.c. apart. The amount of wall between these girder trusses as shown on Sheet 3 of 8 is only 9’-4”. One of the girder trusses will be bearing on the header over a window. Either size this header to account for the point load or move the windows further apart and provide posts under each girder to the foundation.

There are post footings under the one girder truss over the garage; what about the other girder truss over the garage which takes nearly the same load?

Braced walls need to be spaced no further than 25'-0" o.c. [2003 IBC Table R602.10.1]. Therefore an additional braced wall needs to be added to the east exterior wall of the garage.

PLUMBING:

Sheet 2 of 8 makes numerous references to the 1994 UPC with State Amendments. The City of Tucson is currently under the 2003 UPC with local amendments. Please correct all references.

The waste line extension back to the existing storage/carport building will require a cleanout just outside of this structure.

Note and specify all piping materials (water, waste, and gas piping) [2003 UPC Sec. 1209.5, 604, and 715].

MECHANICAL:

There are no mechanical comments to be addressed.

ELECTRICAL:

Note that at least one 20-amp branch circuit shall be installed to serve the laundry room, and this circuit shall have no other outlets [2003 IRC Sec. E3603.3 and E3801.8].

ENERGY:

There are no energy comments to be addressed.

-End of Review-

If you have any questions, please call (520) 750-7474.

Sincerely,
Stantec Consulting Inc.



Joel Svoboda
Associate

JS:js

Attachments: none