Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM05277
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/06/2006 | JWILLIA5 | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Provide structural calculations per IBC 2003, wind and seismic analysis. 2) Provide roof framing plan. 3) Clarify framing connectors. 4) Depth of footing? 5) Clarify electrical requirements for this small building. |
| 10/13/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show how the building complies with the ventilation requirements of Section 401, IMC 2003. |
| 10/13/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 10/13/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/13/2006 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 10/13/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
| 11/08/2006 | CAGUILA1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 11/08/2006 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 11/08/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 11/08/2006 | CAGUILA1 | FIRE | REVIEW | Needs Review |