Permit Number: T06CM05277
Parcel: 10824012B

Address:
2550 E RIVER RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM05277
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/06/2006 JWILLIA5 BUILDING-COMMERCIAL REVIEW Denied 1) Provide structural calculations per IBC 2003, wind and seismic analysis.
2) Provide roof framing plan.
3) Clarify framing connectors.
4) Depth of footing?
5) Clarify electrical requirements for this small building.
10/13/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show how the building complies with the ventilation requirements of Section 401, IMC 2003.
10/13/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/13/2006 ROBERT SHERRY WATER REVIEW Approved
10/13/2006 STEVE SHIELDS ZONING REVIEW Approved
10/13/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
11/08/2006 CAGUILA1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
11/08/2006 CAGUILA1 WWM REVIEW Needs Review
11/08/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
11/08/2006 CAGUILA1 FIRE REVIEW Needs Review