Permit Number: T06CM05268
Parcel: 111073700

Address:
3422 E GLENN ST

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T06CM05268
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2007 MARTIN BROWN FIRE REVIEW Approved
02/13/2007 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: GLENN VERDE CONDOMINIUMS
T06CM05268
Site Plan (3rd Review)

TRANSMITTAL DATE: February 14, 2007

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.), Land Use Code (LUC) & ICC/ANSI A117.1-2003

2. Under the assumption that all units will have a 2nd story addition this plan is reviewed for full code compliance due to a greater then 25% building expansion. Additional comments may be forth coming.

3. The east & west property line dimensions show "309.38 (M), 299.28 (R) & 310.15 (M), 300.09 (R), These dimensions should reflect what is shown on the Final Plat recorded in 1980. D.S. 2-02.2.1.A.5

4. The current bicycle parking calculation shows 49 vehicle parking spaces provided when only 47 are shown on the site plan. Revise the calculation. Under the bicycle parking calculation provide the proposed and provided bicycle parking spaces D.S. 2-02.2.2.A.4

5. An over the counter review may be scheduled once the above comments have been addressed. Call or email to schedule and appointment.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 791-5608 ext. 1180.

C:\planning\site\t06cm05268-3rd.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
02/14/2007 STEVE SHIELDS ZONING HC SITE REVIEW Approved
02/22/2007 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. If temporary use of the MS&R right-of-way is proposed, a site plan/landscape plan is required indicating how the project will comply with LUC requirements when the MS&R right-of-way can no longer be used as part of the site. Such plan is to be an exhibit to an executed covenant for recordation stating the responsibility of the property owner, successor, or assignee as to the removal of improvements and compliance with the LUC at no cost to the City. LUC 2.8.3.5.F.

2. The site plan and landscape plan must show identical site layout to avoid conflict between the two plans. Verify the lot lines on the landscape and site plans are the same (See Zoning comments).

3. A planter area with a minimum unpaved area of thirty-four (34) square feet and a four (4) foot minimum width is required or each canopy tree within the vehicle use area. Note indicating that planters are to be 54" X 54" are not adequate, revise as necessary.Revise

4. The landscape plan to include the following calculations:
§ Length and width of landscape borders and number of canopy trees per length including
§ Square footage of all landscaped areas and calculation of the percentage of vegetative coverage for each type of plant materials per DS 2-07.2.2.A.

5. The planting plan and layout calculations will include the following information both the proper and common name of each type of plant material including vegetation to be removed from site. Indicate type of tree to be demolished.

6. Additional comments may apply
02/22/2007 ANDREW CONNOR NPPO REVIEW Denied The planting plan and layout calculations will include the following information both the proper and common name of each type of plant material including vegetation to be removed from site. Indicate type of tree to be demolished.

Additional comments may apply
02/23/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: February 23, 2007
ACTIVITY NUMBER: T06CM05268
PROJECT NAME: Glenn Verde Condominiums Site Plan
PROJECT ADDRESS: 3422 East Glenn Street
PROJECT REVIEWER: Patricia Gilbert, Engineering Associate

The following items must be revised or added to the site plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: SITE PLAN

APPROVED: DRAINAGE STATEMENT

1. The east and west property dimensions should reflect what is found on the Final Plat recorded
in 1980. Revise plan. See Zoning comment 3. D.S. 2-02.2.1.A.5

2. Revise the length on the near side SVT to 265'. DS 2-01.2.1.A.10., DS 3-01.5.0.

3. Revise the plan view to show the same amount of off site flow entering the site that is provided in the drainage report.

4. Identify detail number and the sheet number the detail can be found for keynote 10.

5. On the plan view the cross section 16/3 is not provided on sheet 3. Correct the label to show the correct sheet number.

6. From cross section 8 on sheet 4 remove the verbiage "R/W Line."

Final Status

Task End Date Reviewer's Name Type of Review Description
03/01/2007 FSANCHE1 OUT TO CUSTOMER Completed
03/01/2007 SUE REEVES REJECT SHELF Completed