Review Details: COMMERCIAL TI

Permit Number - T06CM05260
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/04/2006 MICHAEL ST. PAUL ZONING REVIEW Approved
10/04/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied !. Revise the font sizes to be a minimum of 1/8", all upper case.
2. Show that the sequence of operation for the restroom exhaust fan will not result in recirculation of the air from the restrooms.
3. Reference the use of ASHRAE 62.1-2004 as the method used to calculate the required ventilation.
10/04/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
10/04/2006 ROBERT SHERRY WATER REVIEW Approved
10/04/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied S1. PROVIDE CALCULATION ON ROOF MOUNTED EQUIPMENT.
10/04/2006 PATRICIA GILBERT ENGINEERING REVIEW Approved
10/04/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font sizes to be a minimum of 1/8", all upper case.
2. Provide an additional cleanout for the new 4" building drain for horizontal changes of direction exceeding 135 degrees.
10/05/2006 GBONILL1 WWM REVIEW Needs Review
10/05/2006 DAVE MANN FIRE REVIEW Approved
10/05/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review