Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM05260
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/04/2006 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
10/04/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | !. Revise the font sizes to be a minimum of 1/8", all upper case. 2. Show that the sequence of operation for the restroom exhaust fan will not result in recirculation of the air from the restrooms. 3. Reference the use of ASHRAE 62.1-2004 as the method used to calculate the required ventilation. |
10/04/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
10/04/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/04/2006 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | S1. PROVIDE CALCULATION ON ROOF MOUNTED EQUIPMENT. |
10/04/2006 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
10/04/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the font sizes to be a minimum of 1/8", all upper case. 2. Provide an additional cleanout for the new 4" building drain for horizontal changes of direction exceeding 135 degrees. |
10/05/2006 | GBONILL1 | WWM | REVIEW | Needs Review | |
10/05/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
10/05/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |