Permit Number: T06CM05254
Parcel: 10712242B

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T06CM05254
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2007 GERRY KOZIOL WWM REVIEW Approved
02/20/2007 LINHART PETERSEN POERS ASSOC. 2ND PARTY REVIEW REVIEW Denied February 13, 2007 CITY OF TUCSON - FIRST CHECK
Tucson Appl. No. T06CM05254
Bureau Veritas Job No. 01007-161001.007

Mr Arturo Hernandez
5311 S. Missiondale
Tucson, Arizona 85706


Re: Plan Review: Duplex
Address: 26 E Laguna 1 & 2


Dear Mr. Hernandez,

Bureau Veritas North America has completed a first review of the following documents on behalf of the City of Tucson:

Plans: Two (2) sets of building plans (10 sheets) no dates, no stamps.

Structural Calculations: None submitted with this review.

Truss Calculations: None submitted with this review.


These documents were reviewed only for their conformance to the provisions of the 2003 International Building Codes (i.e., State of Arizona and Tucson amended 2003 IRC, 2003 IMC, 2002 NEC and 2003 IPC).

Please submit an itemized response letter and required number of complete and revised documents with all revisions clouded.


Sincerely,

Bureau Veritas North America



Shelley Knuffke
ICC Plans Examiner








SK:tm s:/tucson\01007-161001.007pc1
enclosures


Re: Stories: One (Duplex)
Occupancy: R-3/VB
Building Area (sq. ft.): 1083 Unit 1 (livable)
971 Unit 2 (livable)
2054 Total sq. ft.

A. The following plan review comments are based on the City of Tucson Building Regulations and referred to the 2003 International Building Code.

B. Please respond in writing to each comment by marking the attached comment list or creating a response letter. Indicate which detail, specification, or calculation shows the requested information. Your complete and clear responses will expedite the re-check and hopefully, approval of this project. Thank you for your assistance.

C. These plan review comments are based on building code items only. If site-related comments are applicable to this project, they will be generated by others (e.g., County Engineering, Public Works, Health, etc.).



ELEVATION COMMENTS:

Indicate all materials used - stucco, concrete block, glass block, roofing systems, siding, veneers, etc. IRC Section R703.

Provide exterior wall covering anchoring method and backing (ICBO Evaluation Report number if applicable). IRC Section R703.7.2.

For thin coat stucco systems over foam board, note and specify the ICBO Evaluation Report number, system name and manufacturer. Note and specify the vapor barrier used.


FOUNDATION COMMENTS:

Foundation plates and sills shall be bolted to the foundation with minimum 1/2 inch bolts at 6 feet or less on center and embedded a minimum 7 inches into the foundation. IRC Section R403.1.6.

Locate and specify all anchor bolt spacing and post anchors on the foundation plan.


FRAMING PLAN COMMENTS:

Rafters must be within the span limitations of IRC Table R802.5.1 (1) through (8). Floor joists must be within the span limitations of IRC Table R502.3.1 (1) and (2). Girders and beams must be within the span limitations of IRC Table R502.5.1 (1) and (2). Rafters are over spanned.

Specify design criteria: floor and roof live and dead loads. IRC Section R301.

Show required holddowns, as specified on lateral design or as required for all alternate braced wall panels, on the foundation plan.

TRUSS SYSTEMS: Trusses can be submitted as a “Deferred Submittal” for custom homes only. However, they must be submitted and approved prior to their fabrication.

If you’re going to use trusses provide complete truss calculations and truss layout plan. Truss designs submitted must include all types and be designed for the loading conditions, span, slope, and spacing designated on the framing plan.


MECHANICAL COMMENTS:

Specify HVAC equipment. IRC Section M1301.3.

Provide a minimum 4 inch diameter moisture exhaust vent for clothes dryer. Indicate size of vent. IRC Section M1501.1.


PLUMBING COMMENTS:

Note that drainage piping serving fixtures which have flood level rims located below the elevation of the next upstream manhole cover of the public sewer shall be protected from backflow of sewage by a backwater valve. IRC Section P3008.


ELECTRICAL COMMENTS:

Provide a convenience receptacle outlet for the servicing of appliances (HVAC) within 25 feet of the appliance. IRC Section 3801. (Rooftop HVAC Units).


If you have any questions regarding the above comments, please contact Shelley Knuffke at (520) 576-8400 between 8:00 A.M. to 5:00 P.M., M-F.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/26/2007 FSANCHE1 OUT TO CUSTOMER Completed
02/26/2007 SUE REEVES REJECT SHELF Completed