Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM05248
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/03/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) It appears that the accessible path to the restroom facilities passes through a storage area. Please comply with section 1104.3 IBC 2003.
10/03/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/03/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM05248 10/3/06

Most of the electrical work is on approved plan set T06CM03865, sealed 7/11/06. Final Electrical inspection has been approved. Please distinguish new from existing circuits for the purposes of this permit.
10/03/2006 ROBERT SHERRY WATER REVIEW Approved
10/03/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the partial demolition plan, 2/P1.
2. Revise the font size on the plumbing fixture and water heater schedules and the water pressure calculations.
10/12/2006 DROBEY1 WWM REVIEW Needs Review
10/12/2006 DROBEY1 ZONING REVIEW Needs Review
10/12/2006 DROBEY1 ENGINEERING REVIEW Needs Review
10/12/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
10/12/2006 DROBEY1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/12/2006 DELMA ROBEY OUT TO CUSTOMER Needs Review
10/12/2006 DELMA ROBEY REJECT SHELF Needs Review
10/12/2006 DELMA ROBEY APPROVAL SHELF Needs Review