Permit Number: T06CM05235
Parcel: 12201024H

Address:
3908 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM05235
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied S1. SEE PRIOR COMMENT #S1. PROVIDE ACCESSIBLE TOILET ROOM FLOOR PLAN AND FIXTURE LOCATIONS AND DETAILS. [S1. CLARIFY ACCESSIBILITY, SHOW AND NOTE ON DRAWINGS WHERE 20% OF PROJECT COST IS SPENT ON ACCESSIBILITY (RESTROOMS) PER IBC SEC 3409 AND ANSI A117.1-2003 ED.]
10/05/2006 DAVE MANN FIRE REVIEW Approved
10/05/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the ventilation calculations per Section 403.3.2, IMC 2003.
10/05/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the design for the relocated lavatory to limit the temperature of the hot water to no more than 110 degrees Fahrenheit.
10/10/2006 EGRANT1 ZONING REVIEW Needs Review
10/10/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
10/10/2006 EGRANT1 WWM REVIEW Needs Review