Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM05235
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/05/2006 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | S1. SEE PRIOR COMMENT #S1. PROVIDE ACCESSIBLE TOILET ROOM FLOOR PLAN AND FIXTURE LOCATIONS AND DETAILS. [S1. CLARIFY ACCESSIBILITY, SHOW AND NOTE ON DRAWINGS WHERE 20% OF PROJECT COST IS SPENT ON ACCESSIBILITY (RESTROOMS) PER IBC SEC 3409 AND ANSI A117.1-2003 ED.] |
| 10/05/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
| 10/05/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the ventilation calculations per Section 403.3.2, IMC 2003. |
| 10/05/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise the design for the relocated lavatory to limit the temperature of the hot water to no more than 110 degrees Fahrenheit. |
| 10/10/2006 | EGRANT1 | ZONING | REVIEW | Needs Review | |
| 10/10/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 10/10/2006 | EGRANT1 | WWM | REVIEW | Needs Review |