Permit Number: T06CM05235
Parcel: 12201024H

Address:
3908 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM05235
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/02/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied S1. CLARIFY ACCESSIBILITY, SHOW AND NOTE ON DRAWINGS WHERE 20% OF PROJECT COST IS SPENT ON ACCESSIBILITY (RESTROOMS) PER IBC SEC 3409 AND ANSI A117.1-2003 ED.
S2. SHOW WIDTH OF CORRIDORS ON FLOOR PLAN 3'8" MINIMUM PER IBC SEC 10.
S3. PROVIDE LOADS/STRUCTURAL CALCULATIONS AND DETAILS FOR INSTALLATION OF X-RAY.
S4. PROVIDE OFFICIAL ADDRESS SLIP FROM PIMA COUNTY FOR COMBINING TWO SUITES INTO ONE.
10/02/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide ventilation calculations. Reference Section 403, IMC 2003.
10/02/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
10/02/2006 ROBERT SHERRY WATER REVIEW Approved
10/02/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a riser diagram to clarify the nature of the plumbing changes to the relocated sink.
2. Show how the current vacuum and compressed air systems are being modified.
10/02/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved 96" RCP under Alvernon at Grant and topography made this proposed work outside of inundated areas.
10/05/2006 DROBEY1 ZONING REVIEW Needs Review
10/05/2006 DROBEY1 WWM REVIEW Needs Review
10/05/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
10/05/2006 DROBEY1 FIRE REVIEW Needs Review