Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM05227
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/29/2006 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 09/29/2006 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 10/02/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM05227 10/02/06 1. Account for continuous loading and largest motor for all phases on Panel K. 2. Demonstrate the Panel A is not overloaded. |
| 10/02/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the new exhaust hood and fan for the 4' hood to show that it complies whith the requirements of Section 506.3.4. 2. Show the construction of the wall adjacent to the new hood. 3. Show how the hood is to be mounted and installed, including any duct shaft or duct fire wrap. 4. If the A/C units are to be providing make up air for the hood, provide an electrical interlock. |
| 10/02/2006 | DAVE MANN | FIRE | REVIEW | Denied | Fire sprinklers required. Please add the following automatic sprinkler criteria to the plans: 1. The hazard classification of the occupancy including any special hazards. 2. The design standard to be used. 3. The availability and adequacy of the water supply. 4. The design density and the area of operation. |
| 10/02/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/02/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide information regarding the gas load of the existing equipment and show the arrangement of the gas manifold. |
| 10/11/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/12/2006 | RSHERRY1 | WWM | REVIEW | Passed | |
| 10/12/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |