Permit Number: T06CM05227
Parcel: 13612833A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM05227
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2006 STEVE SHIELDS ZONING REVIEW Approved
09/29/2006 PATRICIA GILBERT ENGINEERING REVIEW Approved
10/02/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM05227 10/02/06

1. Account for continuous loading and largest motor for all phases on Panel K.
2. Demonstrate the Panel A is not overloaded.
10/02/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the new exhaust hood and fan for the 4' hood to show that it complies whith the requirements of Section 506.3.4.
2. Show the construction of the wall adjacent to the new hood.
3. Show how the hood is to be mounted and installed, including any duct shaft or duct fire wrap.
4. If the A/C units are to be providing make up air for the hood, provide an electrical interlock.
10/02/2006 DAVE MANN FIRE REVIEW Denied Fire sprinklers required.
Please add the following automatic sprinkler criteria to the plans:

1. The hazard classification of the occupancy including any special hazards.
2. The design standard to be used.
3. The availability and adequacy of the water supply.
4. The design density and the area of operation.
10/02/2006 ROBERT SHERRY WATER REVIEW Approved
10/02/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide information regarding the gas load of the existing equipment and show the arrangement of the gas manifold.
10/11/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
10/12/2006 RSHERRY1 WWM REVIEW Passed
10/12/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed