Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM05220
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/18/2006 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 10/18/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/18/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM05220 10/18/06 1. Provide fault calculations for the AFC at new panel. The use of current limiting characteristics of overcurrent protective devices is not acceptable. 2. Plot location of service entrance on scaled plans. |
| 10/18/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/18/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PLEASE PROVIDE STRUCTURAL CALCULATIONS FOR NEW HVAC UNIT ADDED ON ROOF. CLARIFY ROOF CAN CARRY NEW DEAD LOAD. |
| 10/18/2006 | RSHERRY1 | WWM | REVIEW | Passed | |
| 10/18/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 10/18/2006 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 10/18/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/24/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |