Permit Number: T06CM05220
Parcel: 10408084A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM05220
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2006 MICHAEL ST. PAUL ZONING REVIEW Approved
10/18/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/18/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM05220 10/18/06

1. Provide fault calculations for the AFC at new panel. The use of current limiting characteristics of overcurrent protective devices is not acceptable.
2. Plot location of service entrance on scaled plans.
10/18/2006 ROBERT SHERRY WATER REVIEW Approved
10/18/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PLEASE PROVIDE STRUCTURAL CALCULATIONS FOR NEW HVAC UNIT ADDED ON ROOF.
CLARIFY ROOF CAN CARRY NEW DEAD LOAD.
10/18/2006 RSHERRY1 WWM REVIEW Passed
10/18/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/18/2006 PATRICIA GILBERT ENGINEERING REVIEW Approved
10/18/2006 MARTIN BROWN FIRE REVIEW Approved
10/24/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review