Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T06CM05207
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/09/2006 | ANDREW CONNOR | NPPO | REVIEW | Approved | |
10/10/2006 | LINHART PETERSEN POERS ASSOC. | BUILDING-COMMERCIAL | REVIEW | Approved | |
10/10/2006 | BETSY COTTLE | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
10/31/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
10/31/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/31/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The listing information for the specified water fountain indicates a required minimum flowing pressure of 30 PSI. According to Tucson Water, the water pressure range for the project area is 43-50 PSI. Provide calculations to show that the proposed installation will comply with the listing requirements for the water fountain. Reference Sections 103.2.3, 310.4, 608.1, and 610.1, UPC 2003. |
11/01/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
11/02/2006 | GERRY KOZIOL | WWM | REVIEW | Passed | |
11/06/2006 | MARTY DUPONT | ADA | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/16/2006 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
11/16/2006 | SUE REEVES | REJECT SHELF | Completed |