Permit Number: T06CM05189
Parcel: 134220010

Address:
425 S MANN AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM05189
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/22/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Third request. The floor drains shown on sheet P1.0 are code-compliant but the architectural drawing, A1.1 has not been changed to show the floor sloping to the floor drains. Section 412.2.1, UPC 2003 requires the floor to be sloped towards the drain. Note that the "wash out" openings shown on the architectural floor plan cannot be approved without an appeal to the building official.
2. The drawing specifications for the urinal may call for 1 gallon per flush but the manufacturer of the urinal has designed the unit for 3.5 GPF with a 1-1/4" water connection for the flush valve. According to ARS Title 45, Chapter 1, Article 12, this is prohibited. Also, the standard unit is designed to only wash down its back wall at each flush, an insanitary condition per Sections 211.0 and 406.2, UPC 2003. Reference Section 402.1, UPC 2003, as amended by the City of Tucson.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/06/2007 DELMA ROBEY OUT TO CUSTOMER Completed
02/06/2007 DELMA ROBEY REJECT SHELF Completed