Permit Number: T06CM05177
Parcel: 103217550

Review Status: Completed

Review Details: OTHER

Permit Number - T06CM05177
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2006 MICHAEL ST. PAUL ZONING REVIEW Approved
09/28/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM05177 9/28/06

1. Identify panel and circuit for gate operator and loop detector circuit.
2. Show location on plans of electrical panel and loop detector control equipment.
3. Provide cut sheets for gate operator, motor, and loop detector control technology.
4. Provide a disconnecting means for the gate operator motor. Reference NEC 430 Part IX.
09/28/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved SEE CONDITIONS OF APPROVAL.