| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/05/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T06CM05154 10/5/06 1. Revise Electrical Note 1 to indicate 2002 NEC, not 1999. 2. TEP SR-510 calls for 22,000 A available fault current, not 10,000. In any case, this is only applicable for detached single family residences. Provide AFC at this location, and fault current rating of the new equipment. 3. Specify that the breakers for the pumps and compressor be lockable in the open position. Reference NEC 430.102 (B). |