Permit Number: T06CM05154
Parcel: 116094240

Review Status: Completed

Review Details: OTHER

Permit Number - T06CM05154
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T06CM05154 10/5/06

1. Revise Electrical Note 1 to indicate 2002 NEC, not 1999.
2. TEP SR-510 calls for 22,000 A available fault current, not 10,000. In any case, this is only applicable for detached single family residences. Provide AFC at this location, and fault current rating of the new equipment.
3. Specify that the breakers for the pumps and compressor be lockable in the open position. Reference NEC 430.102 (B).
10/05/2006 GERRY KOZIOL WWM REVIEW Approved