Permit Number: T06CM05154
Parcel: 116094240

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T06CM05154
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/26/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
09/27/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM05154 9/27/06
SEE THE ATTACHED ELECTRICAL PERMITTING REQUIREMENTS. DESIGN SHALL INCLUDE BUT NOT BE LIMITED TO THE FOLLOWING.
1. Show each piece of electrical equipment plotted on scaled drawing.
2. Specify conduit and conductor size and type.
3. Provide a disconnecting means for the motors. Reference NEC 430 Part IX.
4. Provide an electrical line diagram of the installation.
5. Provide motor overload protection. Reference NEC 430 Part III.
6. Provide motor ground fault and short circuit protection. Reference NEC 430 Part IV.
7. Specify the Grounding Electrode System, Main Bonding Jumper, Grounding Electrode Conductor, and Equipment Bonding. Reference NEC 250.
8. Provide available fault current.
9. Provide fault calculations.
10. Provide fault current rating of equipment.
11. Provide service disconnect. Reference NEC 230.
10/05/2006 SREEVES1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/16/2006 VFLORES1 OUT TO CUSTOMER Completed