Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM05152
Parcel: 11904600F

Address:
3741 S 12TH AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM05152
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/26/2006 MARTIN BROWN FIRE REVIEW Approved
09/26/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied If the new suite addition is a change of occupancy, provide information regarding the ventilation of the space.
09/26/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM05152 9/26/06

1. Provide panel and circuit for new receptacles.
2. Provide panel schedule and load calculations.
3. Provide for grounding from phone board referenced in Note 5 Sheet A1.01. NEC 800.40.
4. Show single toggle switch from Note 6 Sheet A1.01. Show this switch on the electrical plans and identify "accent lighting".
5. Show power pole from Note 7 Sheet A1.01. Show this power pole on the electrical plans and identify its electrical loads.
6. Regarding Note 13 Sheet A1.01, any new work on any sign shall be documented on these plans and presented for review.
09/26/2006 ROBERT SHERRY WATER REVIEW Approved
09/26/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied S1. RESOLVE EXPIRED PERMITS:
1. T97PL02058
2. T97PL02074.
S2. PROVIDE OFFICIAL ADDRESS SLIP FROM PIMA COUNTY ADDRESSING FOR COMBINING TWO SUITES.
S3. PROVIDE COMPLETED CODE REVIEW CHECKLIST BY ARCHITECT OF RECORD.
S4. SEAL ALL PLANS SUBMITTED INCLUDING SITE PLAN BY ARCHITECT OF RECORD.
S5. PROVIDE CONNECTIONS ON DRAWINGS FOR TOP OF PARTITION WALLS REF DET #1/A1.01 TO STRUCTURE ABOVE.
S6. CLARIFY ACCESSIBILITY SUITE 3731: TO COMPLY FULLY DUE TO CHANGE OF OCCUPANCY FROM M TO B, SUITE 3741 : SHOW ON DRAWINGS WHERE 20% OF CONSTRUCTION COST IN THIS SUITE IS SPENT ON ACCESSIBILITY.
S7.DEFINE FINISHES IN WET AREAS AT TOILET ROOM ,INCLUDING FLOOR.
09/26/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide plumbing design for relocating lavatory and water heater.
2. Resolve expired permit (T97PL02074) - gas pressure test.
10/27/2006 EGRANT1 WWM REVIEW Needs Review
10/27/2006 EGRANT1 ZONING REVIEW Needs Review
10/27/2006 EGRANT1 ENGINEERING REVIEW Needs Review
10/27/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review