Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM05152
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/26/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
09/26/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | If the new suite addition is a change of occupancy, provide information regarding the ventilation of the space. |
09/26/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM05152 9/26/06 1. Provide panel and circuit for new receptacles. 2. Provide panel schedule and load calculations. 3. Provide for grounding from phone board referenced in Note 5 Sheet A1.01. NEC 800.40. 4. Show single toggle switch from Note 6 Sheet A1.01. Show this switch on the electrical plans and identify "accent lighting". 5. Show power pole from Note 7 Sheet A1.01. Show this power pole on the electrical plans and identify its electrical loads. 6. Regarding Note 13 Sheet A1.01, any new work on any sign shall be documented on these plans and presented for review. |
09/26/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
09/26/2006 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | S1. RESOLVE EXPIRED PERMITS: 1. T97PL02058 2. T97PL02074. S2. PROVIDE OFFICIAL ADDRESS SLIP FROM PIMA COUNTY ADDRESSING FOR COMBINING TWO SUITES. S3. PROVIDE COMPLETED CODE REVIEW CHECKLIST BY ARCHITECT OF RECORD. S4. SEAL ALL PLANS SUBMITTED INCLUDING SITE PLAN BY ARCHITECT OF RECORD. S5. PROVIDE CONNECTIONS ON DRAWINGS FOR TOP OF PARTITION WALLS REF DET #1/A1.01 TO STRUCTURE ABOVE. S6. CLARIFY ACCESSIBILITY SUITE 3731: TO COMPLY FULLY DUE TO CHANGE OF OCCUPANCY FROM M TO B, SUITE 3741 : SHOW ON DRAWINGS WHERE 20% OF CONSTRUCTION COST IN THIS SUITE IS SPENT ON ACCESSIBILITY. S7.DEFINE FINISHES IN WET AREAS AT TOILET ROOM ,INCLUDING FLOOR. |
09/26/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide plumbing design for relocating lavatory and water heater. 2. Resolve expired permit (T97PL02074) - gas pressure test. |
10/27/2006 | EGRANT1 | WWM | REVIEW | Needs Review | |
10/27/2006 | EGRANT1 | ZONING | REVIEW | Needs Review | |
10/27/2006 | EGRANT1 | ENGINEERING | REVIEW | Needs Review | |
10/27/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |