Permit Number: T06CM05151
Parcel: 14043011A

Review Status: Completed

Review Details: OTHER

Permit Number - T06CM05151
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/26/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T06CM05151 9/26/06

1. Sign disconnecting means shall be an externally operable switch or circuit breaker. Item 2 on the Cross Section does not appear to be one of these. Reference NEC 600.6.
2. Provide panel and circuit number for the 3 sign circuits.
3. Provide panel schedule and load calculations.
09/26/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Approved S1. PROVIDE LOAD CAPACITY OF BOLTS THROUGH WALL PANEL AND GIRT , SHOW GIRT ON CONNECTION DETAIL.