| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/26/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T06CM05151 9/26/06 1. Sign disconnecting means shall be an externally operable switch or circuit breaker. Item 2 on the Cross Section does not appear to be one of these. Reference NEC 600.6. 2. Provide panel and circuit number for the 3 sign circuits. 3. Provide panel schedule and load calculations. |
| 09/26/2006 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Approved | S1. PROVIDE LOAD CAPACITY OF BOLTS THROUGH WALL PANEL AND GIRT , SHOW GIRT ON CONNECTION DETAIL. |